What size generator do I need to run a heat pump?

A heat pump draws about 4,000 watts running and needs about 9,000 watts for a second or two at start-up. On its own, a heat pump needs a generator rated for at least 4,800 running watts and 9,000 starting watts. A 7,000-watt inverter generator covers it.

A heat pump is the hardest heating system to back up, because in very cold weather it can call for 10 kW or more of electric backup strips on top of the compressor. Ask your installer whether the strips can be locked out on generator power.

Sizes that work

Almost nobody backs up one appliance alone, so the table also shows it alongside two typical household lists. Generator sizes include 20% headroom.

What is runningRunning loadStarting peakEnergy per daySmallest portableSmallest standby
On its own4.0 kW9.0 kW40.0 kWh7,000 W running10 kW
With household essentials7.5 kW12.5 kW51.2 kWh12,000 W running14 kW
With a comfortable list9.3 kW14.3 kW65.0 kWh12,000 W running14 kW

On a battery instead

Power stationRuns a heat pump for
6 kWh whole-home portable battery3.2 hours

Assumes 10 hours of running a day and 88% of the battery's rated capacity reaching the appliance.

Common questions

How many watts does a heat pump use?

Typically about 4,000 watts while running, plus about 5,000 more for a second or two as it starts. Over a day of normal use that is about 40.0 kWh. Your own nameplate is the better number.

Can a battery power station run a heat pump?

Yes. A 6 kWh whole-home portable battery can start and run it, for about 3.2 hours at typical use.